Simulation of neutral point overvoltage and research on new protection measures for 220kV transformer
220kV; transformer; the neutral point; overvoltage; EMTP; protection measure
全文录用
XIUJUAN CHEN / China Electric Power Research Institute
In order to limit single-phase grounding short-circuit current, prevent communication interference and satisfy relay protection setting and configuration, some transformer neutral points often adopt non-grounding operation mode on 220 kV neutral point effective grounding system. During operation, transformer neutral point may withstand the lightning overvoltage, switching overvoltage, single-phase grounding and ground-fault overvoltage, non-full-phase switching overvoltage. Such overvoltage may damage the insulation of transformer neutral point. At present, the neutral point of ungrounded transformer in our country is usually protected by gap and/or arrester. The overvoltage mentioned above may cause misoperation of protection gap or thermal collapse of arrester, which would affect the safe and reliable operation of the system. For this reason, the typical 110 kV system was selected and the typical lightning overvoltage, switching overvoltage, single-phase grounding and ground-fault overvoltage, non-full-phase switching overvoltage applied to transformer neutral point under various operation modes were simulated by electromagnetic transient calculation program (EMTP). Based on the calculated overvoltage values, the insulation protection measures of transformer neutral point were studied and made be reasonable. The parameters configuration and the research results were of great significance to ensure the reliable operation of 220 kV system and the safety of equipment.
重要日期
  • 会议日期

    04月07日

    2019

    04月10日

    2019

  • 04月10日 2019

    注册截止日期

  • 05月12日 2019

    初稿截稿日期

主办单位
IEEE电介质和电气绝缘协会
中国电工学会工程电介质专业委员会
承办单位
华南理工大学
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询