Partial Discharge Detection and Structure Optimization of a Bushing of 10 kV Switchgear Cabinet
switchgear cabinet,bushing,live detection,finite element method,electric field intensity,structure optimization
终稿
Deng Zhixiang / state grid jiangxi electric power research institute
Cai Muliang / state grid jiangxi electric power research institute
Wang huayun / state grid jiangxi electric power research institute
Fan Ruixiang / state grid jiangxi electric power research institute
Zheng Shujiang / state grid jiangxi electric power research institute
Hao Yu / state grid jiangxi electric power research institute
Abstract-Bushing of 10 kV switchgear cabinet is prone to partial discharge. Though live detection can find out partial discharge, the mostly used ultrasonic(AE) and transient earth voltage(TEV) methods have some limitations. This paper introduces a typical case which detected bushing erosion based on ultrasonic(AE) and Ultra-high frequency (UHF) methods. Furthermore, this paper simulates the electric field distribution of bushing using finite element method(FEM), which confirms the live detection conclusion that the metal plate and the busbar were not connected and thus led to local electrical field distortion and suspended discharge. At last, this paper optimized the structure of bushing of 10 kV switchgear based on finite element method(FEM) and insulation structure optimization principles. The optimized bushing of 10 kV switchgear has a significantly better electrical performance and can effectively avoid partial discharge caused by the defects produced during installation and operation.
重要日期
  • 会议日期

    04月07日

    2019

    04月10日

    2019

  • 04月10日 2019

    注册截止日期

  • 05月12日 2019

    初稿截稿日期

主办单位
IEEE电介质和电气绝缘协会
中国电工学会工程电介质专业委员会
承办单位
华南理工大学
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询