652 / 2019-04-22 09:21:17
Transformer Inrush Current Restraining Method Based on Integrated Control of Closing Voltage Parameters
integrated control of closing voltage parameters,no-load closing,restraining inrush current,transformer
终稿
Anxin XU / School of Electrical Engineering,Shandong University
Wei Cong / School of Electrical Engineering,Shandong University
Weixu Wang / State Grid Shandong Electric Power Corporation Maintenance Company
Liqiang Zhang / School of Electrical Engineering,Shandong University
Liangliang Hu / School of Electrical Engineering,Shandong University
A scheme of restraining transformer inrush current is proposed based on integrated control of voltage amplitude and closing angle. In this scheme, the flux does not exceed the saturation flux during the whole process of transformer no-load closing. Considering the different remanence of the transformer, the control strategy and tuning method of the key parameters and closing angle of the voltage amplitude control function are analyzed. The three-phase transformer no-load closing model is built to simulate the method proposed in this paper. The simulation results show that the proposed method can be applied to various no-load closing occasions and has better magnetizing inrush current restraining effect.