Research on phase-by-phase adaptive reclosing sequence for transmission lines
编号:110 访问权限:仅限参会人 更新:2020-11-11 12:09:39 浏览:143次 张贴报告

报告开始:暂无开始时间(12)

报告时间:暂无持续时间

所在会场:[暂无会议] [暂无会议段]

暂无文件

摘要
There is no feasible method to discriminate between permanent fault and transient fault after the three-phase circuit breakers are tripped. The reclosing onto a permanent fault may cause an impact on the system. So a phase-by-phase adaptive reclosing sequence for single-phase earth fault is proposed in this paper. When a fault occurs on the transmission line or reclosing onto a permanent fault, the fault line three-phase circuit breakers are tripped. Then the circuit breaker of the non-fault-phase is closed on one side. Permanent fault is discriminating from transient fault by voltage of fault phase. To permanent fault, the circuit breaker will be tripped again. As for transient fault, the circuit breakers of the rest phases are closed. The PSCAD/EMTDC simulation results verify its correctness and effectiveness.
关键词
adaptive reclosure,phase by phase reclosure,reclosing sequence,permanent fault,reclosing overvoltage