Low-Voltage Ride-Through Control Strategy for Direct-Driven Wind Power System Based on Quasi-Proportional Resonant Controller
编号:123 访问权限:仅限参会人 更新:2020-11-11 12:09:43 浏览:140次 张贴报告

报告开始:暂无开始时间(12)

报告时间:暂无持续时间

所在会场:[暂无会议] [暂无会议段]

暂无文件

摘要
In the case of asymmetric faults in the power grid, the DC voltage of direct-driven wind power system rises with double frequency fluctuation. The cause of the phenomenon is analyzed and a comprehensive low-voltage ride-through control strategy is proposed. The dual current-loop control structure is adopted on the grid side to reduce the distortion of the current at point of common coupling. The control structure based on the Quasi-PR controller is adopted on the generator side to let electromagnetic power of PMSG follow the active power outputted by the grid-side inverter, thereby reducing the difference of active power between two sides of the converter and suppressing rise and double frequency fluctuation of DC voltage.
关键词
Asymmetric fault; Direct-driven wind power system; Fluctuation of capacitor’s voltage; Low-voltage ride-through