Concepts for Secured Protection of VSC HVDC Overhead Lines Equipped with Auto Reclosing of DC Circuit Breakers
编号:222 访问权限:仅限参会人 更新:2020-11-11 12:10:08 浏览:255次 口头报告

报告开始:暂无开始时间(12)

报告时间:暂无持续时间

所在会场:[暂无会议] [暂无会议段]

暂无文件

摘要
We analyzed the transients of DC voltage and DC currents during auto reclosing of HVDC circuit breakers to an overhead DC line fault of a VSC HVDC grid. When the line is energized by reclosing the HVDC breaker the voltage and current transients behave differently from the transient following the initial DC fault. Furthermore, the transients observed during auto reclosing differs between permanent and temporary DC faults. We designed a robust DC line protection system that accounts for the transients following auto reclosing to avoid unwanted trips on the DC line. Numerical tests using PSCAD shows improvement in security of protecting overhead lines in VSC HVDC grids.
关键词
DC Grid, HVDC, DC Overhead lines, Protection, Reclosing