An Identification Method for Sympathetic Inrush Based on Substation-Area Information
编号:247 访问权限:仅限参会人 更新:2020-11-11 12:10:14 浏览:169次 张贴报告

报告开始:暂无开始时间(12)

报告时间:暂无持续时间

所在会场:[暂无会议] [暂无会议段]

暂无文件

摘要
Sympathetic inrush is a phenomenon that occurs in an in-service transformer (IT) when a nearby transformer is energized. The phenomenon can cause transformer differential protection to maloperate. Identification methods for sympathetic inrush have been proposed to deal with the problem. However, these methods are based on local information from the IT, while sympathetic inrush involves two or more transformers. Therefore, an identification method is proposed based on substation-area information. A substation-area differential current is defined and its second harmonic component is utilized to identify the sympathetic inrush. Simulation results by PSCAD/EMTDC show the proposed method can distinguish sympathetic inrush from internal faults and energization inrush effectively.
关键词
differential protection,magnetizing inrush,substation-area information,sympathetic inrush,transformer protection