A Novel Fault Current Limiter for MMC-Based HVDC System
编号:320
访问权限:仅限参会人
更新:2020-11-11 12:10:29 浏览:250次
张贴报告
摘要
In the modular multilevel converter (MMC)-based HVDC system, the fault current rises rapidly when a dc side fault occurs. To avoid the damage to the semi-conductors, fault current limitation is quite necessary. For the fault current limiter proposed in this paper, the current flows through the thyristers in the normal operation state, while it will flow through the current limiting resisters due to the turning off of the thyristers by the commutation capacitor in the case of a dc line fault. To provide theoretical basis to the choice of the main parameters of the fault current limiter, this paper analyzed the current of every branch in the fault current limiter. The simulation results of the model built in PSCAD/EMTDC verified the effectiveness of the fault current limiter.
关键词
MMC,Fault current limitation,Current-limiting resister,Short-circuit fault
稿件作者
Qiang Huang
Shandong University
Guibin Zou
Shandong University
Houlei Gao
Shandong University
发表评论