摘要
Stator winding waterway blockage fault is a serious body fault of water-cooled turbo-generator. Mastering the corresponding law between waterway blockage fault and stator winding temperature distribution is the premise of on-line monitoring and fault diagnosis. In this paper, a three-dimensional thermal network model for calculating the temperature of water-cooled stator winding considering the actual transposition structure is proposed. By comparing with the experimental data, the necessity of considering the transposition structure and the correctness of the calculation results are verified. Furthermore, the temperature distribution law of stator winding under different blocking positions and different blocking numbers of hollow strands is studied, and compared with the temperature distribution law obtained by the existing calculation method without considering transposition structure.
关键词
turbo-generator;waterway blockage fault;thermal network;transposition structure;temperature
报告人
ShijieBao
Master's degree Harbin University of Science and Technology

发表评论
验证码 看不清楚,更换一张
全部评论
重要日期
  • 会议日期

    05月27日

    2022

    05月29日

    2022

  • 02月28日 2022

    初稿截稿日期

  • 05月29日 2022

    注册截止日期

  • 06月22日 2022

    报告提交截止日期

主办单位
IEEE Beijing Section
China Electrotechnical Society
Southeast University
协办单位
IEEE Industry Applications Society
IEEE Nanjing Section
联系方式
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询