Influence of Waterway Blockage Fault on Temperature Distribution of Stator Transposition Winding
编号:484
访问权限:仅限参会人
更新:2022-05-21 15:33:51
浏览:173次
张贴报告
摘要
Stator winding waterway blockage fault is a serious body fault of water-cooled turbo-generator. Mastering the corresponding law between waterway blockage fault and stator winding temperature distribution is the premise of on-line monitoring and fault diagnosis. In this paper, a three-dimensional thermal network model for calculating the temperature of water-cooled stator winding considering the actual transposition structure is proposed. By comparing with the experimental data, the necessity of considering the transposition structure and the correctness of the calculation results are verified. Furthermore, the temperature distribution law of stator winding under different blocking positions and different blocking numbers of hollow strands is studied, and compared with the temperature distribution law obtained by the existing calculation method without considering transposition structure.
关键词
turbo-generator;waterway blockage fault;thermal network;transposition structure;temperature
发表评论