Research on the Influencing Factors of Guano Flashover of TYPE I Composite Insulator on Overhead Transmission Line
编号:62 访问权限:仅限参会人 更新:2022-05-16 09:24:18 浏览:182次 张贴报告

报告开始:暂无开始时间(Asia/Shanghai)

报告时间:暂无持续时间

所在会场:[暂无会议] [暂无会议段]

视频 无权播放 演示文件 附属文件

提示:该报告下的文件权限为仅限参会人,您尚未登录,暂时无法查看。

摘要
Guano flashover is one of the main faults involving birds in overhead transmission lines, which seriously affects the reliability of power grids. In order to determine the effects of different factors on the guano flashover, a 110kV TYPE I composite insulator was taken as an example to design and build a test platform, build 3D electric field simulation models to simulate the guano flashover test, and to study the effects of the guano viscosity, conductivity, whether there was a voltage equalization ring or not, and the dropping path on the guano flashover probability. The results showed that the higher the viscosity of the guano was, the higher the flashover probability was when the distance from the edge of the composite insulator was 15-21cm. The higher the conductivity of the guano was, the higher the flashover probability was when the viscosity was the same. Composite insulators were more likely to flashover when voltage equalization ring was installed than when not installed. The closer the guano plane was to the wire plane, the larger the critical flashover distance was and there was no linear relationship between them.
关键词
transmission line; composite insulator; guano flashover; viscosity; conductivity
报告人
HongWu
Power Research Institute of State Grid Ningxia Electric Power Co., Ltd

发表评论
验证码 看不清楚,更换一张
全部评论
重要日期
  • 会议日期

    05月27日

    2022

    05月29日

    2022

  • 02月28日 2022

    初稿截稿日期

  • 05月29日 2022

    注册截止日期

  • 06月22日 2022

    报告提交截止日期

主办单位
IEEE Beijing Section
China Electrotechnical Society
Southeast University
协办单位
IEEE Industry Applications Society
IEEE Nanjing Section
联系方式
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询