786 / 2022-03-31 22:35:05
Study on Pollution Flashover Characteristics of Inverted T-type Insulator Strings
inverted T‑type insulator string, suspended I string, pollution flashover voltage, comparison
全文被拒
Yafeng Chao / State Grid Hunan Electric Power Company Limited Research Institute
Liu Zhang / Hunan Xiangdian Test & Research Institute Co., Ltd
Pan Zhou / State Grid Xiangtan Power Supply Company
Xiaoliang Peng / State Grid Hunan Extra High Voltage Transmission Company
Yi Xie / State Grid Hunan Electric Power Company Limited Research Institute
Cheng Wang / State Grid Hunan Electric Power Company Limited Research Institute
Insulator arrangement has significant influence on pollution flashover voltage under natural pollution condition. In this paper, the pollution discharge process of an inverted T‑type insulator string is simulated in the artificial climate chamber, and the pollution discharge voltage is compared with the suspended I string. The difference of pollution flashover voltage gradient E50 between two different series types is not obvious. According to the analysis, since the creepage distance, material coefficient and shape coefficient are consistent, the pollution flashover voltage gradient will not be much different.