413 / 2017-04-27 09:51:20
A New Intelligent Controlled Reactor With Controlled Moveable Magnetic-wedge for Fault Current Limiter
Fault current limiter, controlled reactor,magnetic-wedge, fast actuator,magnetic circuit
终稿
Zhihui Huang / Dalian University of Technology
Qitao Zou / Dalian University of Technology
Lin Zou / China Southern Power Grid Company Limited
jiyan zou / Dalian University of Technology
Ruihai Li / China Southern Power Grid Company Limited
Song Wang / China Southern Power Grid Company Limited
A new intelligent controlled reactor (ICR) was proposed. The reactance of ICR can be changed by a moveable magnetic-wedge, and be a large reactance when fault and lower in normal. The electromagnetic model was founded and the magnetic circuit was analyzed, then the design formula of ICR’s reactance was deduced. The structure of ICR was primary designed and modeled by using ANSYS. The equivalent reactance values were simulated when the magnetic-wedge was in different displacements. The result showed that the ICR’s reactance achieved the maximum value when the magnetic-wedge was plug-in completely, and the ICR’s reactance was reduced quickly when the magnetic-wedge was pull-out. The ICR can work with a fast actuator to constitute a fault current limiter that can limit fault current by adjusting magnetic circuit without current converting.
重要日期
  • 会议日期

    10月22日

    2017

    10月25日

    2017

  • 01月04日 2017

    摘要录用通知日期

  • 03月10日 2017

    初稿录用通知日期

  • 06月30日 2017

    终稿截稿日期

  • 10月25日 2017

    注册截止日期

联系方式
  • ice********
  • +86*********
移动端
在手机上打开
小程序
打开微信小程序
客服