443 / 2017-04-29 15:34:02
Assessment of Various Kinds of AC Black- Box Arc Models for DC Circuit Breaker
Arc-Circuit Interactions,Black-Box Arc Models,DC Circuit Breaker,DC Electric Arc Analysis,Parametric Sweep Method
终稿
Bang-Wook Lee / Hanyang University
Kyu-Hoon Park / Hanyang University
Ho-Yun Lee / Hanyang University
Mansoor Asif / Hanyang University
Tae-Yong Shin / VITZROTECH Co., Ltd.
Chi-Wuk Gu / VITZROTECH Co., Ltd.
Many computational techniques which could analyze the behavior of electrical arc have been utilized to estimate the interrupting ability of the circuit breakers. Among them, black-box arc model has been known for valuable tool to simulate dynamic arc-circuit interactions during fault current interruption. Previous research works has shown that the black-box model was efficient tool to analyze AC arc characteristics especially for SF6 and air circuit breakers. But there’s no noticeable investigations about the application of black box model to the DC circuit breakers, which is widely used in DC railway systems and DC microgrid. In this work, we tried to verify the validity of the applications of conventional AC black-box model to the DC electric arc. Several conventional arc models containing Cassie, Mayr and Schwarz model were analyzed considering the tendency of the dc arcing current and voltage waveform using parametric sweep method. Simulation results showed that the weakness of current AC black-box model for DC arc analysis and compared that which model is more suitable for analyzing the DC arc.
重要日期
  • 会议日期

    10月22日

    2017

    10月25日

    2017

  • 01月04日 2017

    摘要录用通知日期

  • 03月10日 2017

    初稿录用通知日期

  • 06月30日 2017

    终稿截稿日期

  • 10月25日 2017

    注册截止日期

联系方式
  • ice********
  • +86*********
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询