Minimum Arcing Interruption Performance of a 126 kV Single-Break Vacuum Circuit Breaker with 3/4 coil type axial magnetic field contacts
14031,14032,13424,minimum arcing contact gap
终稿
Haomin Li / Xi'an Jiaotong University
Zihan Wang / Xi'an Jiaotong Univeisity
Guiquan Han / Pinggao Group Co., Ltd.
Yonglin Li / Pinggao Group Co., Ltd.
Yinghua Bi / Pinggao Group Co., Ltd.
Yingsan Geng / Xi'an Jiaotong University
Zhiyuan Liu / Xi'an Jiaotong University
The objective of this paper is to determine the minimum arcing interruption performance of a 126 kV single-break vacuum circuit breaker with 3/4 coil-type axial magnetic field contacts in test duty T100s. The full contact gap was 50 mm. A Spring type mechanism was used to provide an average opening velocity of 3.0 m/s within 20 mm after contacts separation. Test duty T100s experiment with a rated short circuit current of 40 kA rms was carried out by using current injection synthetic test method. The experiment results show that the minimum arcing time was determined as 4.8 ms. The corresponding minimum arcing contact gap was determined as 14.4 mm. Further analyses indicate that with increasing of contact gap from 11.7 to 25.8 mm in the experiment, phase shift time decreased from 0.84 to 0.63 ms. While residual axial magnetic flux density at current zero decreased from 153.25 to 89.97 mT. Phase shift time and residual axial magnetic field of 126 kV single-break vacuum circuit breaker at minimum arcing contact gap were 0.77 ms and 136.22 mT, respectively.
重要日期
  • 会议日期

    10月22日

    2017

    10月25日

    2017

  • 01月04日 2017

    摘要录用通知日期

  • 03月10日 2017

    初稿录用通知日期

  • 06月30日 2017

    终稿截稿日期

  • 10月25日 2017

    注册截止日期

联系方式
  • ice********
  • +86*********
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询